Responded to no heat call for 2-year-old furnace. Found system switched off at equipment disconnect. Restored power and verified proper operation. Completed scheduled maintenance service, which included inspection of heat exchanger showing signs of corrosion and examination of evaporator coil with visible frost accumulation. Advised customer to cancel separately scheduled maintenance appointment.