Responded to no heat call for 5-year-old Lennox furnace exhibiting lockout condition due to pressure switch calibration failure. Diagnosed improper furnace pitch causing secondary heat exchanger condensate leakage. Corrected installation pitch per manufacturer specifications, cleaned pressure switch lines, and replaced pressure switch assembly due to potential corrosion from moisture exposure. Verified proper operation through multiple test cycles with continuous monitoring.