David B.

David B. Job Checkin

AOR callback for PVC leaking at joint. Cut out and removed leaking joint and replaced with new fittings. Checked for leaks - All okay at this time. Thanks Mike. No charge, AOR Callback.

AOR callback for PVC leaking at joint. Cut out and removed leaking joint and replaced with new fittings. Checked for leaks - All okay at this time. Thanks Mike. 

No charge, AOR Callback.

David B.

David B. Job Checkin

I am unable to perform a tune-up. All wiring inside the outdoor condenser unit is burnt up. A mouse took residence inside the compressor blanket and chewed and shorted the wires on the compressor heater, causing all the wires to burn up. The unit cannot run, so I don’t know if the internal compressor wiring is also shorted. The unit is 12-13 years old. Turn information over to Ian to talk with the customer about replacing the air conditioner and maybe the furnace.

I am unable to perform a tune-up. All wiring inside the outdoor condenser unit is burnt up. A mouse took residence inside the compressor blanket and chewed and shorted the wires on the compressor heater, causing all the wires to burn up. The unit cannot run, so I don’t know if the internal compressor wiring is also shorted. The unit is 12-13 years old. Turn information over to Ian to talk with the customer about replacing the air conditioner and maybe the furnace.

David B.

David B. Job Checkin

CCC AC tuneups Air conditioner preventive maintenance Check filters, Check contactors and capacitors, check all motors including compressor. Check refrigerant charge and temps in system. Pull covers and clean condenser coil. All checks good at this time. Filter 20x25x4 replaced with truck stock . Age of unit 2021 Refrigerant R410A on TXV Outdoor temp. 38 degrees Capacitor 45/5 Actual 44.5/4.6 Compressor amps. 4.6 Condenser fan motor 0.6 amps Charge, unable to check due to outdoor temp Filter 20x25x4 replaced with truck stock Age of unit 2021 Refrigerant R410A on TXV Outdoor temp. 38 degrees Capacitor 45/5 Actual 43.5/4.8 Compressor amps. 4.2 Condenser fan motor 0.6 amps Charge, unable to check due to outdoor temp Filter 16x25x4 clean, Age of unit 2021 Refrigerant R410A on TXV Outdoor temp. 38 degrees Capacitor 45/5 Actual 44.2/4.7 Compressor amps. 4.3 Condenser fan motor 0.6 amps Charge, unable to check due to outdoor temp We now offer generator installation, se


David B.

David B. Job Checkin

Preformed commercial AC maintenance on (1)RTU and (1) Split AC unit. See form. Used -(1)A48 belt -(4)20x20x2 Filters -(1)16x25x4 Filter Office to invoice.


David B.

David B. Job Checkin

Completed Preventative maintenance. Oil\filter, air filter, battery test and inspect, inspect all electrical and fuel connections, c\o cabinet. While pulling spark plugs, found the rear cylinder plug was cross threaded or over tightened at the factory causing damage to cylinder head. After several attempts, I was able to remove spark plugs assess the damage, and take some photos for the warranty repair claim. I was able to put anti-cease on new spark plug and thread back into cylinder head to keep generator in operation until repair can be made.