CCC AC tuneup -prepaid Air conditioner preventive maintenance Check filters, Check contactors and capacitors, check all motors including compressor. Check refrigerant charge and temps in system. Pull covers and clean condenser coil. All checks good at this time. Daikin Filter 16x25x4. Replaced with truck stock. Age of unit 20 Refrigerant R410A on TXV Outdoor temp. 36 degrees Capacitor 35/5 Actual 34.5/4.8 Compressor amps. 4.6 Condenser fan motor 0.6 amps We now offer generator installation, service, and repair Have a great summer, Dave


David B.

David B. Job Checkin

Ac tuneup. Tech- Jacob Refrigerant type- 410a Suction line pressure- 103 Suction line temp- 45 Liquid line pressure- 215 Liquid line temp- 65 Superheat- 13 Subcool- 8 Return temp- 63 Supply temp- 45 Temp drop across coil- 18 Dual capacitor specs- 45/5 +\-6% Dual capacitor actual- 42.2/4.9 (failing) also terminals were very rough and corroded. Compressor amps- .70 Condenser motor amps-5.73 Filter- 16x25x4 (good) System is from 2008. While there were no signs of leaks in the system, the system is definitely showing its sign of age. The capacitor was failing and the wire that connects the capacitor to the contactor was fried. This could be from a couple different issues but one of the concerning ones is the compressor is starting to over amp. Showed owner the bad capacitor and went over options. He would just like to replace capacitor at this point in time. Replaced capacitor and test ran and all operations are normal at this time. Thank you, Jake.


David B.

David B. Job Checkin

Ac tuneup. Tech- Jacob Refrigerant type- 410a Suction line pressure- 113 Suction line temp- 45 Liquid line pressure- 220 Liquid line temp- 85 Superheat- 8 Fan speed-good Return temp- 69 Supply temp- 47 Temp drop across coil- 22 Dual capacitor specs- 75/10 +/- 5% Dual capacitor actual- 76.29/10.24 Compressor amps- 9.7 Condenser motor amps- 1.9 Filter- recommend replacing soon. (Owner Replaces) System is operating at manufacturer specifications at this time. Thank you, Jake.

Ac tuneup.
Tech- Jacob
Refrigerant type- 410a
Suction line pressure- 113
Suction line temp- 45
Liquid line pressure- 220
Liquid line temp- 85
Superheat- 8
Fan speed-good
Return temp- 69
Supply temp- 47
Temp drop across coil- 22
Dual capacitor specs- 75/10 +/- 5%
Dual capacitor actual- 76.29/10.24 
Compressor amps- 9.7
Condenser motor amps- 1.9
Filter- recommend replacing soon. (Owner Replaces)
System is operating at manufacturer specifications at this time. Thank you, Jake.

David B.

David B. Job Checkin

MagicPak Install

MagicPak Install

David B.

David B. Job Checkin

CCC AC tune ups Air conditioner preventive maintenance Check filters, Check contactors and capacitors, check all motors including compressor. Check refrigerant charge and temps in system. Pull covers and clean condenser coil. All checks good at this time. Comfort maker Filter 20x25x4 replaced with truck stock Age of unit 2021 Refrigerant R410A on TXV Outdoor temp. 35 degrees Capacitor 45/5 Actual 44.5/5.1 Compressor amps. 4.6 Condenser fan motor 0.6 amps Charge, unable to check due to outdoor temp Filter 16x25x1 clean Age of unit 2020 Refrigerant R410A on TXV Outdoor temp. 35 degrees Capacitor 35/5 Actual 34.5/5.1 Compressor amps. 3.3 Condenser fan motor 0.7 amps Charge, unable to check due to outdoor temp We now offer generator and water heater installation, service, and repair Have a great summer, Dave


David B.

David B. Job Checkin

Tried to set timer it was not me that unplugged unit .