N6705 State Hwy 25
Durand, WI 54736
715-283-4422

Our Top Cities


Local Reviews
for new glarus, wi


Job Locations
for new glarus, wi

David B.

David B. Job Checkin

Furnace had fire in burner box. Rollout code and high limit. Adequate gas supply and venting appears fine. Did temporarily jump rollouts and ran for 10 minutes with no issues. Disabled again for safety reasons. Have calls into tech supt to no avail and left message with Charlie. Damaged parts: Plastic intake plate Vent pipe Top of cabinet Burner box Burner box gasket Burner box door Burner box door gasket Sight glass Flame sensor Flame sensor wire Wire harness 2 rollout switches Possibly inducer and gas valve


David B.

David B. Job Checkin

I was called to a home to repair a broken air conditioner. I found that the unit was tripped on limit, 60 dt, 24ppm, and the exhaust and filter were dirty. I cleared the trap, inspected the exhaust, and filter, and pulled the filter. The unit continued to run without shutting down, so I gave the customer information on the warranty and filters and maintenance. I also explained that the unit was operating properly.


I was called to a home to repair a broken air conditioner. I found that the unit was tripped on limit, 60 dt, 24ppm, and the exhaust and filter were dirty. I cleared the trap, inspected the exhaust, and filter, and pulled the filter. The unit continued to run without shutting down, so I gave the customer information on the warranty and filters and maintenance. I also explained that the unit was operating properly.

BESbswy