CCC AC tuneup -prepaid Air conditioner preventive maintenance Check filters, Check contactors and capacitors, check all motors including compressor. Check refrigerant charge and temps in system. Pull covers and clean condenser coil. All checks good at this time. Daikin Filter 16x25x4. Replaced with truck stock. Age of unit 20 Refrigerant R410A on TXV Outdoor temp. 36 degrees Capacitor 35/5 Actual 34.5/4.8 Compressor amps. 4.6 Condenser fan motor 0.6 amps We now offer generator installation, service, and repair Have a great summer, Dave