Ac tuneup. Tech- Jacob Refrigerant type- R-22 Suction line pressure- 59 Suction line temp- 52 Liquid line pressure- 140 Liquid line temp- 64 Superheat- 5 Subcool- 9 Fan speed-good Return temp- 67 Supply temp- 55 Temp drop across coil- 12 Dual capacitor specs- 30\5 +\- 6% Dual capacitor actual- unable to test due to blown capacitor. Compressor amps- .6 Condenser motor amps- .7 Filter- ok (owner replaces) This system is 25 years old. It is on its last leg. The capacitor was blown. It allowed the system to start up, but after I took it out to show owner, once re installed it started the compressor but not the fan. Went over options with homeowner and stated that putting the cost of a new capacitor into a system that is already barely running is not a good idea. Spoke with Ian about setting up a time to come out here to give a quote on a new air conditioner. He will be in touch to set up a date to do so. Until then the unit is not functioning due to bad capacitor. Thank you, Jake. Office