Upon arrival met with homeowner and homeowner stated that unit would run for 20 minutes and then cut off and this would happen at regular intervals. Did a walk-through inspection with homeowner gave him the option to do magnets or one time inspection. Customer chose to become a maintenance customer. Upon inspection of air handler Found blower and evaporator cool to be dirty. Drain to be clogged. Filter was new. So left a 14 x 25 by one filter replacement. Completely cut out drain and took it outside to clean it. As well as the condensate pump. Thoroughly clean both pieces and reinstalled. Tested thoroughly. Drain is working well now as well as condensate pump. Upon startup of air conditioner pressure is low running 95/265 with a sub 14. Condenser coil is dirty as well. As well as leaking traitor and service valve on the suction. Took findings to homeowner and he agreed to do some deep cleanings. Coil blower and condenser coil. We’re all cleaned. Schrader valve was replaced. Pressure di