The reason we came out today is for no cool. Upon Inspection found zone system that controls both upstairs and downstairs on a 2.5 ton heat pump. Upon inspection of the indoor system found no UV protection. No bypass damper for pressure relief when only one zone is working. Customer has no TE standard flood protection, only flood protection she has is a bulldog float switch. This float switch could fail. Upon inspection of no cool found system totally out of refrigeration. Customer approved to do a leak search with nitrogen. The nitrogen leak search indicated where the leak was and it was on the Schrader valve on the AC coil leaking. Found no other leaks present in the system.. Cleaned outdoor unit from all debris and coils. Recharge system with 7 pounds of 410 a. System currently has a 21° delta T and is working properly.
Make all repairs necessary to restore the unit to full health and eliminate all other concerns.
Rewired light with 120v led bulbs to bypass bad ballast
Found leak in crawlspace, coming from a cpvc female on a copper male. Replaced female with ametal cpvc female. Teated to find no leaks.
For this job we investigated why power was off to four outlets in the garage/basement room and replaced a GFCI. We could not find out what was causing the outlets not to work but we believe there is a buried junction box in the ceiling. We gave the customer other options to have power in the room.
For this job we completed a troubleshoot for two rooms not working and completed a full re-device of both rooms including new boxes.