I’ve used TE on a couple of occasions, and each time I received excellent service, I was pleased with all aspects of my service experience. Very professional, courteous and great prices.
Overall Experience
Quality
Price
Convenience
Overall Experience
Quality
Price
Convenience
Replaced water heater, Prv and installed new water heater shut off. Also we replaced the single wall vent with double wall vent and insulated the water lines to bring everything to code. The homeowner did also have a sewer backup which resulted in water coming out from the base of 2 toilets which was from when the homeowner was running the water to release the air from the system. I recommend they reach out to a septic company to inspect the septic tank/leech field.
Pull and reset with minor rebuild on hallway toilet. Previous flange was damaged, replaced with new flange
Estimate - New exterior main breaker panel - Power disconnect with Walton EMC - Pull permit with Walton County
Customer wanted to replace two toilets in the master bathroom and in the sons bathroom, customer supplied two glacier Bay power, flush toilets, and I removed the toilets and replace the new ones with the new wax seal caulk, and new nylon bolts in China caps as well after testing. It was no leaks in the toilets flushing perfectly, didn’t see anything wrong with the flange
Cut open drywall ceiling to search for compromised sections of 3/4” cpvc piping. Found sections of pipe that are stretched beyond the original manufactures design. Suggest repiping sections of waterlines with new piping.
Came out due to the ceiling falling from water damage. Upon inspection of the system found that the drain line was clogged up, and very slow to drain. Also found that this is heil air handler in attic and the extra PVC drain ports from the coil. We’re not capped off, allowing free flow once the water reached that level of the drain pan. Also performed a fully evaluation over the equipment found that the indoor coil was very rusty, the indoor blower motor had a large amount to build up, also found biological growth throughout the entire system in the attic. Upon inspection of the outdoor system found the condenser coil is dirty, the outdoor capacitor was bad and out of range from what factory says, also throughout testing the system found it as low on 410 a refrigerant. Due to the buildup on the system cannot get an accurate reading of refrigerant one system is cleaned. It would indicate the system is also lower on charge than what it is reading now. Upon speaking with the homeowner he
Replace high chandelier and high ceiling fan Replace dining room light Troubleshoot hallway lights
For this I worked on replacing breaker on main panel for AC unit that was downsized. Also replaced defective weatherproof outlet in basement entrance
Homeowner had us out today due to the main floor system not cooling. Upon arrival we noticed that there is a system that is from 2014. We noticed that the main breaker for the system trips after five seconds of runtime. We checked the electrical on the outdoor unit and found that the 45/5 capacitor was completely dead and needed to be replaced. We also noticed that the compressor amps were higher than listed on the data plate and recommended installing a hard Start kit. We also noticed some biological growth on the inside of the unit and recommended UVC light. Homeowner opted to replace capacitor and install hard start kit. System is cooling at time of departure.
Replaced 1/2 hp disposal with 3/4 hp disposal. Tested with no leaks and working properly
Install new customer supplied water heater in basement /well system with bladder and recirculating line existing (no circulation pump present)