Returned 6/8 to install the capacitor, contactor and a hard start kit. I ran the system for 30 minutes checked pressures, temps and the system is running according to specifications.
Came out to a no cool. Found that the system was not compressing, we checked all components and the capacitor was dead and the co factor was failing. The system was also amping high at the start up so we would like to add a hard start kit to the unit. The customer declined all options as he stated that the mark up on the parts were to high.
Return today to complete work. Upon arrival, reclaimed all refrigerant out of system. Replace coil on the indoor unit, clear, drain line, and change outdoor capacitor. Put vacuum down to below 500 microns and recharge system. Tested system to come to ensure operation is proper. At this time, there is no other concerns with the downstairs system. This system is working properly.
Came out today because the downstairs system is not cooling. Upon inspection found that the downstairs system had a restriction in the metering device. The system does not have TE standard flood protection. This system does not have any UV protection. This system is a Bryant air handler and heat pump from 2020. Upon inspection of the system found that the systems coil is very dirty and could possibly have other restrictions in it. Due to system still being under warranty will replace coil and TXV. upstairs system Customer says it is working properly. Will need to return once coil arrives to complete work.
Shut Off valve for the water heater is leaking. I shut off the water to the home and drained the system. Removed a section of the cpvc along with the shut off valve and replaced with copper and a ball valve. Turned on the water and pressurized the water system. No further leaks detected.