James D.

James D.


Job Checkin

We came out today to install the Grounding Electrode System on the home along with a full home surge protector. -Grounding Electrodes Conductor- We installed one grounding electrode from the main breaker CH panel across the basement then dropped come recess lights in the finished portion of the basement and over to the PRV and jumped it along with making contact within 5’ of entry. We installed another grounding electrode conductor from the main breaker panel over to the exterior wall by the back door and went outside to the ground rods. -Ground Rods- We installed (2) 8’ rods into the earth past the new deck to allow rain to make contact to the rods. I preformed a Fall Of Potential test on each electrode to see where the resistance value was at. *Rod by the fence 48.3 Ohms *Rod closet to the home 51.2 Ohms I then ran a temporary bonding jumper between each new rod in parallel and the resistance value dropped down to 27.7 ohms. After bonding the hot and cold at the water heat