Upon arrival found breaker tripped. Before I reset the breaker I checked the capacitor. Found the cap to be bad, replaced cap and reset breaker system started up, let system run for about 45 min noticed that my pressures were abnormal. Had very high head pressure and sub cooling, superheat was low. Rinsed down the outdoor coil and let run. Same subcooling and super heat. Checked my Delta T that was also high. Determined that the system may have a restriction and the compressor is on it way out. Recommended recovering refrigerant, replacing compressor, filter dryer, capacitor and contactor. Also recommend adding a hard start. At this time customer chose to do the bandaid option and just change the capacitor. Informed customer that the system still has some issues and is not going to run correctly. Left quote for full repair. Customer will reach out when ready.