2 System Inspection Cycled each system through heat and cool from the thermostat. Changed both 1 inch filters, flushed drain lines with 2 gallons of hot water, took temperature readings at indoor equipment, inspected heat exchangers, blower motors, and coils. Checked and tightened all electrical connections, used multimeter to check all motors, power enhancers, and high wear components. The main level system is right at 15 years old and has some major concerns regarding the Gas Furnace. There are multiple cracks and small rust holes In the Heat Exchanger. The blower wheel is dirty/impacted with debris, which is reducing air flow across the heat exchanger and coil. The inducer motor is over amping, the hot surface igniter is weak and failing, the flame rectifier is also weak and reading below manufacture parameters, and the condensation pump ran for over 15 minutes trying to pump out water. The impeller is dirty and damaged. Due to the age, condition, multiple parts outdated, and th