Annual Fire Extinguisher Inspection (4 units) Annual Exit/Emergency Lighting Inspection (3 units) Semi-Annual Kitchen Hood Fire Suppression System Inspection (Ansul 3gl) Deficiency: Number of Systems failed : 1 Horn / Strobe only operates when exhaust fan is ON. Make-up Air does NOT turn OFF when ON if system is activated Exhaust fan does NOT turn ON when OFF if system is activated Added single-burner stove does not have detection or protection Portable Extinguishers, Emergency / Exit Lights, and Kitchen Suppression Inspection