Tyler H. Job Checkin

Annual Fire Alarm Inspection - Notifier SLG 404 21 devices


Jim S.

Jim S. Job Checkin

9/10/21  confirmed with Nick for Monday   9/13/21  SM 8/12 Requested by and confirmed with Dan, owner.   His cook will come in early to let you in. km Portable Extinguishers and Kitchen Suppression Inspection Annual Fire Extinguisher Inspection (2)ABC's (1)BC (1)K-Class Semiannual Kitchen Suppression System Inspection ( 1 RG725 ) Deficiency: 1 5lb abc Ansul was condemned needs to be replaced. Need additional 2 units to bring restaurant up to NFPA 10 code. Deficiency: Number of Extinguishers Left at Job: 1 Deficiency: Number of Systems failed : 1 Deficiency for Range Guard RG 6G+2.5G Wall Across from Main Hood: System does not have a discharge warning device. Deficiency for Range Guard RG 6G+2.5G Wall Across from Main Hood: Electric non fuel source on convection oven and 110v outlets under main hood do not de energize upon fire system actuation.


Jim S.

Jim S. Job Checkin

7/2/21  confirmed with Mark for 7/6/21   sM Portable Extinguishers Inspection Annual Fire Extinguisher Inspection (4 FE) Inoperable Deficiency for 2.5 lb ABC VAN: 2.5lb ABC in Van has been discharged. Recharge needed. Deficiency: Number of Extinguishers Left at Job: 1


Tyler H.

Tyler H. Job Checkin

EMCOR Paperwork Attached Annual Fire Alarm Inspection


Alex R.

Alex R. Job Checkin

Completed Annual Fire Extinguisher and Emergency light Inspections for 2021


Alex R.

Alex R. Job Checkin

Completed Annual Fire Extinguisher and Emergency light Inspections for 2021


Mark S.

Mark S. Job Checkin


John  R.

John R. Job Checkin


John  R.

John R. Job Checkin


Alex R.

Alex R. Job Checkin

Completed Annual Fire Extinguisher Inspection for 2020


Alex R.

Alex R. Job Checkin

Completed Annual Fire Extinguisher Inspection for 2020


John  R.

John R. Job Checkin


Tony K.

Tony K. Job Checkin

There is a short reporting on Main Panel NAC 2 even though wiring disconnected and end of line resistor in its place.


Tony K.

Tony K. Job Checkin

System is going in and out of NAC trouble every 20 seconds.


Alex R.

Alex R. Job Checkin

Completed annual Fire Alarm and Extinguisher inspections for 2019