did not go up into the attic to find the leak that a tech found the next morning
Sprinkler Emergency Service Call Emergency service call for: Site has a leak in the dry pipe sprinkler system with the air compressor kicking on every 5 minutes.
9/12/23 Sent email regarding inspection and Backflow information. DH Backflow and Sprinkler Inspection Annual Backflow Inspection (2 Backflow Preventers) Quarterly Sprinkler Inspection (2 Wet and 1 Dry system)
per mike move to july GB Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet, 1 Dry System) ***Next Full Flood Due: PAST DUE Deficiency: Wet and Dry system gauges are outdated and shall be replaced with new. 2- water 2- air Deficiency: Painted concealed covers shall be replaced with new. All in social Room and men’s room 20- white Viking 404 concealed covers Deficiency: Wet and Dry system gauges are outdated and shall be replaced with new. 2- water 2- air Deficiency: A 5yr internal inspection shall be performed on system piping. Lift required. 2- 4” grv coup 1- 2 1/2” 1- 2” Deficiency: A 5yr internal inspection shall be performed on FDC check valve. 2- 4” grv coup Deficiency: mproper amount of spare heads/style available in head box heads shall be installed. 1- head box 1- 1/2 155 QR brass upright 3- 1/2” 155 QR Chrm HSW Deficiency: Painted concealed covers shall be replaced with new. All in social Room and men’s room 20- white Viking 404 concealed covers Deficiency: An Aut