2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Local Reviews
for east grand rapids, mi

Rated 5.0 out of 5 stars based on 2 customer reviews

Excellent Work

  • Overall Experience
  • Quality
  • Price
  • Convenience

Custodial Supervisor

I felt that the service tech's did probably the most thorough job that I have seen in recent years. The advice on current safety such as the firehoses in our performing arts center was most helpful. Great service with a smile, thanks guys. Bruce Towne Jr. EGR Custodial Supervisor

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for east grand rapids, mi

Brandon  F.

Brandon F. Job Checkin


Brandon  F.

Brandon F. Job Checkin


John  R.

John R. Job Checkin


Gary B.

Gary B. Job Checkin

Per Caleb they have electricians out right now and they accidently set off the kitchen system and need it recharged Suggested for RANGE-GUARD RG-4GM 4 GALLON MAIN HOOD / KITCHEN: System dumped when electrician went to run lines in the ceiling and moved the ceiling tile. Remote pull station conduit must have moved and dumped system.. There is MINIMAL room between ceiling tiles and ceiling, so could not get any pictures of conduit. Recommended to owners that they have Fire Pros return and run pull station conduit and wire below ceiling and have it mounted securely. Cannot investigate link line conduit in ceiling due to no ability to move ceiling tiles. Link line conduit is loose going above ceiling tiles. NEED TO QUOTE: (1) stick conduit (4) corner pulleys ((20’) cable (2) crimp (2) hours labor for (1) tech. (6) conduit clamps to firmly secure remote station link line conduit


John  R.

John R. Job Checkin


Sean W.

Sean W. Job Checkin


Gary B.

Gary B. Job Checkin

Deficiency for Ansul R102 1.5 gallon Main kitchen: Number of Systems failed : 1 Electrical connections are made inside system cabinet. They need to be made in outside junction box. NEED ELECTRICIAN Semi-annual Kitchen Suppression System Inspection (Ansul R102 1.5gal AB) (Range Guard w/Badger head 1.25g)


Gary B.

Gary B. Job Checkin

Semi-annual Kitchen Suppression System Inspection (Ansul R102 1.5gal AB) Deficiency for Ansul R102 1.5 gallon Kitchen: Number of Systems failed : 1 System wiring connections are inside system cabinet Connections need to be made in an outside junction box. NEED ELECTRICIAN


Gary B.

Gary B. Job Checkin

Semi-annual Kitchen Suppression System Inspection Cafeteria -RG 6 Gal Badger Head Concession Stand - PCL 1.6 Ga


John  R.

John R. Job Checkin


Gary B.

Gary B. Job Checkin

Annual Fire Extinguisher Inspection (14 FE) Semi-annual Kitchen Suppression System Inspection (Ansul R102 1.5gal AB) (Range Guard w/Badger head 1.25g)


John  R.

John R. Job Checkin


John  R.

John R. Job Checkin


Art L.

Art L. Job Checkin

Annual inspection of (98 FE's) Semi-annual Kitchen Suppression System Inspection RG 6 Gal Badger Head MAIN HOOD PCL 1.6Gal


Art L.

Art L. Job Checkin

Portable Extinguishers Inspection