Sprinkler Emergency Service Call There is a lo-air supervisory on the panel. It seems they have a leak in the dry system. This has been an issue in the past. Site is requesting emergency service for today. Repair of Low air supervisory dry system has leak 3rd floor pump rm pumped system back to normal pressure and cleared panel
2/21/24 Sent email regarding DH Sprinkler Inspection Annual sprinkler inspection Deficiency: Sprinkler system is due for gauge change. 1- sprinkler gauge Deficiency: Sprinkler system is due for five year internal obstruction investigation of piping. 2- victaulic couplings Deficiency: Number one control valve needs sign. 1- control valve sign Deficiency: There is no evidence of five year sprinkler system fire department, connection, Hydro test. Deficiency: Sprinkler system is due for five year internal inspection, Fire department connection check valve. 2- 4” victaulic couplings
2/21/24 Sent email regarding inspection DH Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: Missing, concealed head wrench, in head box for a tyco 3531 Deficiency: Fire sprinkler system is due for gauge change. 1- sprinkler gauge Deficiency: The sprinkler system is due for five year internal inspection, fire department, connection, check valve. 2- victaulic couplings Deficiency: Sprinkler system is due for five year internal obstruction investigation of piping. 2- 4” victaulic couplings Deficiency: One control valve sign for lower control valves needed. 1- control valve sign Deficiency: Fire sprinkler system is due for five-year Hydro test. Deficiency: Missing, concealed head wrench, in head box for a tyco 3531