David was very good and professional. The adjustments that were made in regards to contact prior to service was very welcome. Thank you. the turn around for report was super awesome.
W side of building next to produce prep / ITV: in mech rm behind meat prep: Remove and replace the dry pendents in the cooler and freezers that are dated between 1992 - 1993. NFPA 25 (5.3.1.1.6) Dry sprinklers that have been in service for 10 years shall be replaced or representative samples shall be tested and then retested at 10-year internals.