6” Wet riser, back of building in storage area in 108C, ITV same area, feeds dollar store and suit: Remove and replace (2) outdated water gauges. 6” Wet riser, back of building in storage area in 108C, ITV same area, feeds dollar store and suit: Perform a 5-year internal assessment of system piping that is due. If an obstruction is present, this can render the sprinkler system not properly operate in the case of a fire. NFPA 25 (14.2.1.1) An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years or in accordance with 14.2.1.2 to inspect for the presence of foreign organic and inorganic material. 6” Wet riser, back of building in storage area in 108C, ITV same area, feeds dollar store and suit: Perform a 5-year internal inspection of the system check valve. NFPA 25 (13.4.1.2) Alarm valves and their associated strainers, filters, and restrictions orifices shall be inspected internally every 5 years unless tests indicate a greater frequency i
Annual Fire Extinguisher Inspection (6 FE) Portable Extinguishers Inspection
Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection
Portable Extinguishers and Kitchen Suppression Inspection