-Tripping Breaker- At the service disconnect located on the right side of the house has two AC breakers along with 2pole 60 amp breaker that feeds the pool pump panel within the fence. The customer stated that he has been having issues with the two pole 25 amp GFCI breaker tripping. He also stated to me that he has noticed it’s been tripping more frequently. I performed a ground fault current test on the equipment, grounding conductors along with the equal potential bonding conductor for the pool and was getting abnormally high milliamps of current on the equipment grounds. Both the heater and the pump are tied onto the same contactor inside of the pool pump panel and they are both being fed off the two pole 25 amp GFCI breaker. As I started separating these units and watching my meter, it was determined that the issue was coming from the water heater due to the mA being high after turning on the unit and when turned on everything would appear normal on the screen the an error would f