Tech was out for no cooling. There is 2 systems in clinic one does one side of clinic and the other does the other half of clinic. Tech found blown compressor . Wire going to contactor is burnt. Some wires inside condenser unit rubbing. This is caused by not properly securing wires. Contactor burnt due to burnt wire. Compressor was replaced at some time. Reason why compressor failure is due to over size equipment and zoned. System is a 5 ton system. This is to big to cool just one side of health Clinic . 2.5 ton should have been used. 1 damper motor has been disconnected due to motor failure it has been bypassed to stay open. Other damper motor is premature, failing. Zone board wiring is needing to be rewired properly. Wiring is tied into other wires. There are no safety switches on drain line or wet switch in drain pan. Filter is needing to be replaced. Filter has not been replaced since 2023. Tech let Jordan know that if he does go with repairs we can not guarantee that compressor wo