Homeowner had us out today due to the main floor system not cooling. Upon arrival we noticed that there is a system that is from 2014. We noticed that the main breaker for the system trips after five seconds of runtime. We checked the electrical on the outdoor unit and found that the 45/5 capacitor was completely dead and needed to be replaced. We also noticed that the compressor amps were higher than listed on the data plate and recommended installing a hard Start kit. We also noticed some biological growth on the inside of the unit and recommended UVC light. Homeowner opted to replace capacitor and install hard start kit. System is cooling at time of departure.