Leaking cpvc 3/4 supply line on water heater. The leak was caused by unsupported thermal expansion tank, which has failed and is full of water, leaning on and bowing the pipe. The failed thermal expansion tank was caused by excessive pressure. Proper correction of the issue will include new pressure regulator and thermal expansion tank as well as a partial repipe of water heater. Also replaced damaged t&p valve.