10/6/22 Confirmed with Bill for 10/10/22 9:30ish / Sent email regarding inspection DH Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: There is no evidence of 5 year internal pipe obstruction investigation. Deficiency: There is no evidence of 5 year FDC check valve inspection. Deficiency: There is no evidence of FDC hydrostatic test. Deficiency: Quick response sprinkler heads are outdated.