ANNUAL FIRE HYDRANT TEST, FLUSH AND INSPECTION (4 outside hydrants - The #5 Hydrant is being tested by the city / township) Fire Hydrant Inspection ANNUAL FIRE HYDRANT TEST, FLUSH AND INSPECTION (4 outside hydrants - The #5 Hydrant is being tested by the city / township)


Jim S.

Jim S. Job Checkin

7/23 Critical Appt., corp inspection!  Please don't miss!  Confirmed with TJ km 7/6 Confirmed with Karen, GM km Semiannual Kitchen System Inspection Ansul R102-S3 (3)360 links (4)Nozzles Ansul R102-S3 (3)360 links (5)Nozzles Ansul R102--S3 (1)280 link (4)Nozzles Deficiency: Number of Systems failed : 3 Deficiency for Ansul (Filet Fryer) R-102 3 Gallon Right of Hood: All three systems have electrical connections made inside of automan. Deficiency for Ansul (Filet Fryer) R-102 3 Gallon Right of Hood: All three do not have a discharge warning device. Inoperable Deficiency for Ansul (Filet Fryer) R-102 3 Gallon Right of Hood: 101-20 cartridge in Filet Fryer system does not have an Ansul seal. Kitchen Suppression Inspection