Sprinkler Inspection Annual Sprinkler Inspection (1 Wet Sprinkler System) Deficiency: There is no evidence of five-year internal obstruction investigation performed on this system 2- Victaulic Couplings 3” Deficiency: There is no evidence of a five-year internal inspection of fire department connection check valve. 2- Vitalik Couplings 4” Deficiency: There is no evidence of five-year Hydro test on fire department connection


Alex H.

Alex H. Job Checkin


Terrence  J.

Terrence J. Job Checkin

Sprinkler Inspection **Commercial Fire Paperwork** Annual Fire Sprinkler System Inspection Deficiency: Pressure gauge is outdated. Deficiency: QR sprinkler heads are over 20 years. A percentage shall be sent out for UL testing.


Alex H.

Alex H. Job Checkin


Alex R.

Alex R. Job Checkin

Completed annual Fire Extinguisher inspection for 2021