Tech was out today for no heat , found circuit board not putting 120 volts out to blower. Tech bypassed circuit board to verify blower still working. Blower motor failed. Blower not coming on. Hot surface igniter oxidized not glowing completely. Flame sensor needing to be cleaned. Blower wheel needing to be cleaned. Need to replace blower capacitor. Condensate pump failed. No safety switches on evap or drain pan. out door unit not coming on. We have voltage when contactor is push in voltage is not going through other side of contactor. Capacitor failed. No condenser pad underneath condenser. Condenser is needing a chemically cleaning. System needs a Hard start on compressor, System is a R-22 with any repairs tech makes we can not guarantee that system will run due to any other issues after repairs are made. Spoke with customer about issues customer is wanting a quote before making any repairs. Based on our findings today, it might be time to think about getting a brand new system.