Upon arrival customer stated that ac system had been leaking downstairs when running. After inspection of 3 year old heat pump system found that system had a very clogged drain line causing the water to back up in system. Blower wheel is clean, evaporator coil is clean, system is coming on and cooling inside. Customer replaced (16x20x1) system filter. Checked over all operations of outdoor system, contactor tested good, condenser coils were clean, outdoor capacitor on herm terminal for the compressor was testing bad. Gave customer estimate to clean drain line, add wet switch, add in line flood protection, change bad outdoor capacitor and add Uv light to system. Customer only wanted to have drain line cleaned at this time. Removed drain line and cleaned and cleaned evaporator coil drain pan. Flushed system and unit back up and working. Recommended homecare maintenance plan for system, customer not interested at this time.