Completed homecare maintenance for two systems. Fully tested from thermostats and heating and cooling. Well testing I found that the starting components for the main level condenser are failing. Also both systems do not have TE standard flood protections. Calculated airflow for both systems and found that the main level is short on return air and could use a 10 inch duct add-on. Today we completed repairs on the main level system that included replacing the capacitor, contactor, and adding a hard star kit. Tested system fully and no failures at this time.