2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for baldwin, mi


Map of Baldwin MI
Gary B.

Gary B.


Job Checkin

Semi-annual Fire Extinguisher Inspection - (8 FE's) Semi-annual Exit & Emergency Lighting Inspection - (11 lights) Semi-annual Kitchen Suppression System Inspection - PCL 3.5 gal Portable Extinguishers, Emergency / Exit Lights, and Kitchen Suppression Inspection Deficiency: Number of Systems failed : 1 NO Audio/Visual notification Make-up air does NOT shut down when system activated PCL-360 cylinder due for hydro test and recharge Quote: (1) PCL-360 cylinder hydro test (1) PCL-360 recharge (1) valve rebuild kit (1) service collar (1) hour labor 1 tech Need electrician for other deficiencies