Rated 4.7 out of 5 stars based on 3 customer reviews

Annual Inspection

Thorough and professional

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

Friendly

Art was super friendly and made great conversation, and worked quickly and efficiently!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Very good service

Service was friendly and efficient!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for berrien springs, mi

Tyler H.

Tyler H. Job Checkin

Annual Fire Alarm Inspection


Brandon  F.

Brandon F. Job Checkin


Brandon  F.

Brandon F. Job Checkin


Tyler H.

Tyler H. Job Checkin

Sent down to test sensitivity of the new smoke detectors that were added and also test them as well. Panel had troubles on it upon arrival. Troubles on zones 2 & 4. All except the North Hall and office smoke were fine. Office smoke was not replaced and needed to be. Hall smoke had no power. Found smoke was not wired correctly. Rewired smoke and tested. Working properly. Replaced smoke detector in office and tested. Working properly. Figured out the troubles on the panel zones was because there were no End of Line resistors on those loops. Who ever changed the smoke detectors out didn’t put them back in place when they replaced them. Panel still shows a NAC 3 trouble upon departure. Advised customer of the situation and told her we would have to make another service call to track the issue out. This call is for finishing fixing the panel troubles.


John  R.

John R. Job Checkin


John  R.

John R. Job Checkin


Brandon  F.

Brandon F. Job Checkin


Art L.

Art L. Job Checkin

Kitchen Suppression Inspection


Gary B.

Gary B. Job Checkin

Annual Fire Extinguisher Inspection (23 FE) Annual Exit & Emergency Lighting Inspection (25 units)


Tyler H.

Tyler H. Job Checkin

Annual Fire Alarm Inspection


Tyler H.

Tyler H. Job Checkin

NAC JANITOR'S CLOSET: Booster panel 1 in janitors' closet is not charging the batteries and needs to be replaced. ALTRONICS AL400ULADA - This quote is for the replacement of the bad power supply AL602UL-ADA "Wasn't able to get power supply instead went with a AL842ULADA


Sean W.

Sean W. Job Checkin


Tyler H.

Tyler H. Job Checkin

false trip on Zone 3 smokes , he resets it and it trips again. Inspection sheet shows three smokes - two in band rooms and one in office.


Tyler H.

Tyler H. Job Checkin

Annual Fire Alarm Inspection


Mike R.

Mike R. Job Checkin

Sensitivity Testing (29 smoke detectors) Annual Fire Alarm Inspection (48 devices) (Cerberus Pyrotronics SLX)