Sent down to test sensitivity of the new smoke detectors that were added and also test them as well. Panel had troubles on it upon arrival. Troubles on zones 2 & 4. All except the North Hall and office smoke were fine. Office smoke was not replaced and needed to be. Hall smoke had no power. Found smoke was not wired correctly. Rewired smoke and tested. Working properly. Replaced smoke detector in office and tested. Working properly. Figured out the troubles on the panel zones was because there were no End of Line resistors on those loops. Who ever changed the smoke detectors out didn’t put them back in place when they replaced them. Panel still shows a NAC 3 trouble upon departure. Advised customer of the situation and told her we would have to make another service call to track the issue out. This call is for finishing fixing the panel troubles.
Annual Fire Extinguisher Inspection (23 FE) Annual Exit & Emergency Lighting Inspection (25 units)
NAC JANITOR'S CLOSET: Booster panel 1 in janitors' closet is not charging the batteries and needs to be replaced. ALTRONICS AL400ULADA - This quote is for the replacement of the bad power supply AL602UL-ADA "Wasn't able to get power supply instead went with a AL842ULADA
false trip on Zone 3 smokes , he resets it and it trips again. Inspection sheet shows three smokes - two in band rooms and one in office.
Sensitivity Testing (29 smoke detectors) Annual Fire Alarm Inspection (48 devices) (Cerberus Pyrotronics SLX)