Obstruction Investigation, Sprinkler, and Hydrostatic Testing Repair
Obstruction Investigation, Sprinkler, and Hydrostatic Testing Repair
Hydrostatic Testing and Sprinkler Repair
Annual Fire Alarm Inspection (29 devices) (Honeywell Ademco Vista 128FBP)
Annual Fire Alarm Inspection (79 devices) (EST quick start)
Wet In closet by front door On riser: Perform a 5-year internal inspection of the Fire Department Connection (FDC) check valve. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition. Wet In closet by front door On riser: The tech will replenish the missing sprinkler heads in the spare headbox. Wet In closet by front door On riser: The outside PIV control valve is missing supervision. The tech will add supervision to prevent tampering with. Wet In closet by front door On riser: The current anti-freeze system's expansion tank is for potable water and not UL listed. The tech will replace the tank with a fire protection-rated type. Wet In closet by front door On riser: INFORMATIONAL PURPOSE ONLY: The information attached to the anti-freeze system indicates what the system protects, the type of solution, and the amount of solution used in the system is missing. The c