Responded to no heat complaint on a 2-year-old furnace system that was tripping on pressure switch. Diagnosed issue as frozen condensate drain trap caused by cold air intake positioned adjacent to the trap. Temporarily replaced inducer motor for diagnostic purposes, which confirmed the source of high-pitch noise was not the inducer itself. Cleared and cleaned the frozen drain trap, which resolved the operational issues and restored proper system function.