Blanked thermostat due to wet switch activated. Reset wet switch and restored power to thermostat. System was little low on Freon. Added Freon to bring pressures back to normal. Xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx Failed inspection. Mini split condenser is too close to the wall, according to the inspector and need to be moved away from the house. Mini split head in the back room is leaking water thru the drain, and it was installed too close to the ceiling and can’t have access to check drain , neither filter. It need to be moved to other wall in the bedroom. Drain line outside was connected to the gutter , but it’s not downward and water is backing up into the mini split. Will have install crew to fix these issues.