Troubleshoot outlets and fan not working Customer states his son got shocked by touching the subpanel. I check and the subpanel box has 120v to ground. I opened the subpanel and noticed the ground and neutrals are bonded in the subpanel. The ground do and neutrals need to be separated to remedy this problem