Homeowner had us out today because they say the system is short cycling and is not cooling properly. Upon arrival we noticed there is a Goodman furnace that is from 2010. We noticed that the blower motor and the capacitor are super worn out the blower motor is over at 9.3 and the capacitor is a 20 MFD reading 3.3. We also noticed that there is no flood protection on the system which we recommend. Homeowner approved to have repairs made. After repairs were made we verified proper operation on the system