System not cooling - upper level - 18 year old builder grade equipment System not cooling due to multiple reasons. The dual power factor enhancer that starts the compressor and fan motor has failed. The electromagnetic contactor is burnt and pitted hindering voltage flow. The fan motor is getting extremely hot. The windings in both the fan motor and compressor are outside of manufacturer parameters. The system operates on R-22 refrigerant. R-22 Refrigerant is no longer available, nor are refrigerant related components. This is due to the Government Mandated Phase Out of the refrigerant. After going over the age, condition, refrigerant type, and no warranty/guarantee of run time due to these conditions, I recommended updating the equipment. The homeowner requested to have an install supervisor come out to go over updating this system. I scheduled this for tomorrow morning 8-10am. Thank you for choosing T.E. Certified, have a great day!