Came out today to to perform upstairs system no cool service call. Upon arrival, customer stated that the fan on the outside system is not spinning. Upon inspection of the outdoor system found bad capacitor on the Herm side, the condenser coil is dirty, the wires for low-voltage are exposed copper on both units, the condenser fan motor is bad. Inspection of the indoor system found bad indoor blower capacitor, the blower wheel is dirty, the indoor coil has rust on coil, there is no flood protection. Customer wants to schedule install supervisor and is speaking with her home warranty company to see how she wants to move forward. At this time, the upstairs system is not currently working, and I left disconnect and the off position, so no further damages are made. Customer is aware if repairs are made that this could be an ongoing issue and more issues will appear.