As we arrived back here today, December 1, we’ve come back to fulfill the estimate for installing four new dedicated circuits and receptacles and specific locations. After talking with Kendall, he had decided to move all four receptacles over to the area farthest away instead of separating them in two separate areas. We first installed a 3/4 EMT pipe from the electrical panel up the wall and across the warehouse about 75 feet to the location of the four new quad receptacles. At each location I installed metal 1900 box with raised covers and two 20 amp duplex receptacles in each box. Each box has its own dedicated 20 amp circuit. We pulled four dedicated circuits of THHN wire from the electrical panel to each of the junction boxes. All receptacles and metal boxes were properly bonded together. Last time installed four 20 amp single pole Square D QO breakers in the electrical panel and wired all circuits up. Once that was done and breakers were turned on all receptacles worked properly