Came out today because customer found water in his basement around his AC unit. Upon inspection of the system found Goodman system from 2010. Heat pump air handler. Upon testing the system found system was about 2 pounds low on 410 a, the outdoor contactor had stuck together, causing the system to run all the time, even when no call was presented, the outdoor capacitor was weak. It was a 70/5and it was reading 31/4.5. The indoor capacitor for the blower motor was also bad, this was a 25 mfd and evading 21. This system also had no UV protection time presenting all options to homeowner. He decided to do the Band-Aid repair. Will need to return Monday to install a new 25MFD blower capacitor. System is up and running, and once we return with the parts, there will be no other immediate issues with this system.