No cool for basement system is garage * R 22 system dated for 1986 carrier..furnace was just installed recently after asking questions with mother and daughter ..2024 Run Tru furnace …no flood protection on drain line on indoor coil above electrical components ….water was in drip pan as well upon arrival ..vacuumed water and tested out system pressures .tested out drip on flood protection which it works … * R22 evaporator / indoor coil looks to be punctured …company who replaced furnace..supported duct work with straps ran into the side of coil with screws puncturing indoor coil which in turn will CAUSE LEAKS or crack pan if not careful , when they replaced furnace …and I saw water form in bottom of return plenum … and will cause indoor coil to * FREEZE * especially on a older coil … ( see photos ) …Ductboard plenum wrapped in insulation with with gray tape , tried verify if coil pan was cracked with inspection camera and could find any evidence …system has high sub cooling in the