Service no cool …single system conditioning 3 floors ..one thermostat on main level …older pilot furnace …blower wheel heavily consumed with dust / debris and motor could fail at any moment due what I found here .. * defective capacitor for system …did thorough inspection of system and found some additional issues of course listed at the top …pressures were very high after replacement of capacitor…86 degrees in home ..main level ..outside disconnect is bridged and can’t add new disconnect , had to shut breaker to cut off power to check capacitor ……not enough wire to properly install new disconnect … also alluded to pulling and cleaning the blower wheel is unwise due to age of system, * UNIT WILL BE UNDER STRAIN WITH THESE HOT TEMPERATURES * gave client a variety of options including blower and blade replacement and explained to client why that isn’t a great idea on 1988 furnace …* *client selected immediate repair option * ..did eventually accept..replacement option …* pilot furnace a