Homeowner had us out today because the system is not cooling. Upon arrival we noticed that there is a Goodman unit from 2018. We noticed that the outdoor unit was not running on a call for cooling. We tested electrical and found that we were not getting 240 V outside to the unit. We checked the breaker and found that the breaker was tripped. After resetting the breaker, we tested all the other electrical and noticed that the contactor and capacitor are worn out and will need to be replaced. We also noticed that the Outdoor coil is very dirty and needs to be clean. Homeowner approved to have all repairs made. System is cooling at time of departure.