SERVICE CALL: upon arrival homeowner stated the second floor System is not working properly on cooling mode. After complete troubleshooting I found the heat pump system Goodman 3 ton capacity 10 years old is in poor maintenance conditions the blower wheel it’s Highly impacted the indoor evaporator coil is highly impacted and creates Airflow restrictions test outdoor heat pump unit the Duel run capacitor failed is out of spec from manufacture test temporarily capacitor check refrigerant charge pressures are low compressor is weak condenser coil It’s dirty. Perform courtesy electronic leak search for indoor evaporator coil And is leaking refrigerant coil is made of aluminum can’t be repaired Needs to be replaced air handler drain line is not protected with Safety float switch unit is out of warranty I already verified warranty Was expired on 4/21/2025. Due to aged and conditions vs costs of repairs I recommend to upgrade complete system. Homeowner is aware of the Conditions