Homeowner had us out today because she noticed some water leaking on the ceiling. Upon arrival we noticed that there is a five year old carrier system inside of the home. We seen that the emergency drain pan was full of water and the primary drain was completely clogged. We also noticed some biological growth on the inside of the system. We unclogged the drain and poured 4 gallons of water to ensure that the system was no longer clogged. We also noticed that the system is not up to TE flood protection standard and recommended installing a wet switch. We checked refrigerant pressures which were with the manufacture specifications. We also checked electrical and found that the 70/5 capacitor was out of range and needed to be replaced. Homeowner approved to have drain cleaned and wet switch installed