2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Local Reviews
for muskegon heights, mi

Rated 5.0 out of 5 stars based on 5 customer reviews

Fast response

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great

  • Overall Experience
  • Quality
  • Price
  • Convenience

Fire Drill!

Kamp is an excellent partner!


Response from Fire Pros, LLC:

Thank you for leaving a review, we greatly appreciate your feedback! Camp is an awesome asset and we want to create value for you and your organization, Thanks again and have a fire safe day! Also if you have time, please visit Google and leave us a review there as well, we would greatly appreciate it!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Camp is Excellent!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

Matt was wonderful

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for muskegon heights, mi

Mike R.

Mike R. Job Checkin

Suggested: There are 7 manual pulls in gymnasium. 5 of the 7 are missing the cages to protect from damage or false alarm when struck by a ball, body, or anything else. They all had cages at one point they have been broken over time. (1 pic of one with and 1 without) I suggest either covering the other five with a low profile Quickstop cover or, Removing the two cages covering all seven with a low profile quick stop cover for uniformity. All pulls mounted to block wall, no extended boxes. Deficiency: Simplex smoke detector is damaged. Safety cover to protect sensor area is broken off and missing.This smoke detector should be replaced for continued proper operation. Located on cafeteria side of fire door entering cafeteria area from office hall. MODEL # 4098-9714 Head is NOT addressable (base holds dip switches)


Mike R.

Mike R. Job Checkin

Inoperable Deficiency: Div 3: Simplex panel having issues. Upon arrival reset key was in the “reset” position. When reset key is in normal position all zones go into alarm and alarm sounds. Only way to silence is to engage key, but panel won’t reset. “Oper. Pow. Trouble” lights is also on, switch is currently toggled to silence to inhibit piezo from sounding. Very old 120v panel with no battery back up. THIS is for the main school system. Panel does not function as installed, need Simplex or authorized dealer to repair, if possible.


Mike R.

Mike R. Job Checkin

This Quote is for Fire Pros to install Stopper 2 audible covers on all pull stations .


Jason  Z.

Jason Z. Job Checkin

Alarm Systems Inspection


Mike R.

Mike R. Job Checkin

Suggested: FACP shows...OPER. POW. TROUBLE.. This panel has no back up batteries, checked AC voltage it is good at a solid 122.2 V Checked all fuses and re seated them, all fuses are good. Tested NAC it is good. Send signal to monitoring over phone line.Trouble light is still on. I suggest customer calls Symplex to have a technician check why operating power trouble light is on. Was told by staff on site there was a power outage in Muskegon Heights a few days ago, issue could be related to power outage or power restoral


Mike R.

Mike R. Job Checkin

Deficiency for DD POOL MEZZANINE: Duct detector in pool mezzanine for AHU #2 Is corroded and not being seen by panel. This is an addressable SIMPLEX duct detector. The main FACP is a SIMPLEX 4020


Mike R.

Mike R. Job Checkin

Deficiency for DD POOL MEZZANINE: Duct detector in pool mezzanine for AHU #2 Is corroded and not being seen by panel. This is an addressable SIMPLEX duct detector. The main FACP is a SIMPLEX 4020


Mike R.

Mike R. Job Checkin

Service call to check system, testing in trouble mode daily


Ron  R.

Ron R. Job Checkin


Mike R.

Mike R. Job Checkin

per Dawn her monitoring company is calling her at night, her panel is testing in trouble .Service to check.


Art L.

Art L. Job Checkin

Portable Extinguishers Delivery


Art L.

Art L. Job Checkin

Portable Extinguishers Inspection


David H.

David H. Job Checkin


Art L.

Art L. Job Checkin

Semi-Annual Kitchen Suppression System Inspection Annual Fire Extinguisher Inspection (27 FE)


Art L.

Art L. Job Checkin

Portable Extinguishers Inspection