2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Local Reviews
for muskegon heights, mi

Rated 5.0 out of 5 stars based on 5 customer reviews

Fast response

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great

  • Overall Experience
  • Quality
  • Price
  • Convenience

Fire Drill!

Kamp is an excellent partner!


Response from Fire Pros, LLC:

Thank you for leaving a review, we greatly appreciate your feedback! Camp is an awesome asset and we want to create value for you and your organization, Thanks again and have a fire safe day! Also if you have time, please visit Google and leave us a review there as well, we would greatly appreciate it!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Camp is Excellent!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

Matt was wonderful

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for muskegon heights, mi

Mike R.

Mike R. Job Checkin

Local bell is loose and can be tightened, need to replace bell. (1) 110V Horn/Strobe with weather proof box Caulk Hardware to mount to brick wall Riser in boiler room in mechanical room across from kitchen/ gym Breaker in located in electrical room across from boiler where riser is, panel marked as Emer LTG panel, breaker #6 Sprinkler system has own shut off, do not need to shut down water to entire building - repair


Ron  R.

Ron R. Job Checkin


Ron  R.

Ron R. Job Checkin


Mike R.

Mike R. Job Checkin

Annual Fire Alarm Inspection (346 devices)


Mike R.

Mike R. Job Checkin

Annual Fire Alarm Inspection (49 devices)


Mike R.

Mike R. Job Checkin

per james order a new simplex 4098-9714 smoke for gym area.


Mike R.

Mike R. Job Checkin

Deficiency for SD AUDITORIUM CEILING LIGHTING MEZZ: Smoke alarm located above the cat-walk above the stage in auditorium mounted to the ceiling is damaged and, giving a no answer trouble on the Simplex FACP. Jim Hicks stated they have had a lot of roof work a lot of pounding right above there and there is water on stage floor within 1 to 2 feet of smoke detector. **I am unable to get to that smoke detector now for model number but, all other smoke detectors on this site are 4098-9714**


Mike R.

Mike R. Job Checkin

Mike to meet new maint supervisor and show panels, how to check, how to reset. Calling CMS etc. While onsite verify that signals are coming in properly- Dawn mentioned getting messages from CMS that they were not.


Ron  R.

Ron R. Job Checkin


Ron  R.

Ron R. Job Checkin


Gary B.

Gary B. Job Checkin

Portable Fire Extinguishers-NFPA 10 Code: From our recent Inspections, we noted the following service needed for 2020 code compliance - (4) Fire Extinguishers missing from cabinets and (2) other units outdated for required service. (6) NEW 5#ABC EXTINGUISHERS PROPOSED TO REPAIR Portable Extinguishers Repair


Art L.

Art L. Job Checkin

Portable Extinguishers Inspection


Art L.

Art L. Job Checkin

Portable Extinguishers and Kitchen Suppression Inspection


Mike R.

Mike R. Job Checkin

There are 7 manual pulls in gymnasium. 5 of the 7 are missing the cages to protect from damage or false alarm when struck by a ball, body, or anything else. They all had cages at one point they have been broken over time. (1 pic of one with and 1 without) I suggest either covering the other five with a low profile Quickstop cover or, Removing the two cages covering all seven with a low profile quick stop cover for uniformity. All pulls mounted to block wall, no extended boxes. - repair Simplex smoke detector is damaged. Safety cover to protect sensor area is broken off and missing.This smoke detector should be replaced for continued proper operation. Located on cafeteria side of fire door entering cafeteria area from office hall. MODEL # 4098-9714 Head is NOT addressable (base holds dip switches) - repair


Mike R.

Mike R. Job Checkin

Suggested: There are 7 manual pulls in gymnasium. 5 of the 7 are missing the cages to protect from damage or false alarm when struck by a ball, body, or anything else. They all had cages at one point they have been broken over time. (1 pic of one with and 1 without) I suggest either covering the other five with a low profile Quickstop cover or, Removing the two cages covering all seven with a low profile quick stop cover for uniformity. All pulls mounted to block wall, no extended boxes. Deficiency: Simplex smoke detector is damaged. Safety cover to protect sensor area is broken off and missing.This smoke detector should be replaced for continued proper operation. Located on cafeteria side of fire door entering cafeteria area from office hall. MODEL # 4098-9714 Head is NOT addressable (base holds dip switches)