Kitchen Suppression Inspection 7/25 Scheduled with Mrs. Bateman, she confirmed personnel will be on site for alarms. Ask for Mr. JR or Ms. Angie upon arrival km 6/27/2024 1:35 PM need to make return trip for KITCHEN inspection as employee who deals with the alarm info was off for the summer. Semi-Annual Kitchen Hood Fire Suppression System Inspection Deficiency: System is not UL-300. Tilt Skillet is unprotected. Electric fuel source under the hood for all appliances does not shut down during system actuation. Hood penetrations do not have UL-Listed quick seals(8). Detection has two piece link holders that are bent severely and need to be replaced(5).