Diagnosed and resolved no heat complaint on 8-year-old Lennox furnace. Found faulty thermostat showing continuity between G and Y terminals when off, and discovered high limit switch shorting against heat exchanger with visible burn marks on shield. Replaced thermostat, high limit switch, and control fuse. Conducted operational testing to confirm proper system function with all issues resolved.