Diagnosed electrical issue with recently installed IBC boiler that was causing repeated circuit breaker trips. Found defective neutral connection with 120V present on L1 to ground but no voltage from hot to neutral. Restored proper electrical connections, verified system operation, and confirmed stable heating function for in-law suite.